Single Burner Incinerator Portable Incinerator, No Scrubber Cap. 0.01 m3/hour

Single Burner Incinerator Portable Incinerator, No Scrubber Cap. : 0.01 m3/hourType of Waste : Laboratory Waste / Medical Waste

Incinerator Capacity : 0.01 m3/hour
Incinerator Type : Single Chamber
Operation Time : 8 hour/day
Chamber Volume : – 1st Chamber 0.024 m³
Incinerator Dimension (Outter ) : L0.47 x W0.32 x H1.67 m
Burner: 1st Burner 5 – 10 liter / hour, Light Oil Burner, Qty : 1 unit
Chamber Temperature : Chamber ±900°C
Chamber Pressure : Negatif (Under Atmosferic Pressure)
Exaust Stack
– Diameter : 4 inchi
– Height : ± 2 m.from ground level
– Coating : High Temp.Paint
Refractory Construction :
– Fire Brick : Fire Brick SK 32
– Castable : CAJ-12
Chamber Insulation
– 1st Wall : Fire Brick, SK-32
– 2nd Wall : Ceramic Fibre, 128 kg/m³
– Bottom : Insulating Brick
Shell & Structure Material Chamber :
– Shell Plate t.3 mm ,Mild Steel
– Joint Flange t.10 mm
– Burner Port t.8 mm
– Structure UNP 80 &
– Coating : Epoxy Paint
FDF Blower : Sentrifugal ,2500 CMH, 220/50,2800 rpm, 1 unit
Electric Power Requirement : 3 kW. 380 V. 3 PH
Fuel : Diesel Oil ( Solar )
Fuel Consumption : Max.10 liter / hour
Fuel Tank :
– Cap. 10 ltr
– Material Tank : Mild Steel plate t. 3 mm
– Level Control
– Drain Port
Control System :
– ELC
– Temperature Control : Digital
– Thermocouple : Type – K.
– Limit Switch
Ash : 5 – 10 % waste weight
Ash Discharging : Manual
Feeding System : Manual
Warranty Term : Six month ( Service)
Operator Requirement : 1 Person
Area Requirement : 2 x 3 m

Tinggalkan Balasan